EMM.630 CT-MID: Energy Meter 3F on 1A/5A CT, MID, Modbus+pulse

€229,90 (Incl BTW)

The 3F Energy Meter with 1A/5A CT is an advanced 3-phase energy meter with a direct connection to the power grid for measuring reference voltages and 3 terminals for connecting the 1A/5A CTs, allowing for the measurement of loads with >, and 100A. The meter is configured using the touch-sensitive buttons on the front panel and the LCD display. The bidirectional measurement tracks consumption on single-phase, 3x230V, or 3x380V+N power supplies. Both active and reactive power are measured. Consumption values can be viewed on the display or on the connected web server. The module is housed in a 4-module-wide DIN rail enclosure. In addition to an RS485 connection, this energy meter also has 2 pulse outputs, 1 of which is configurable.

  • DIN rail with 4 terminals for connecting power coils (various types)
  • 4 mains connections for measuring reference voltages
  • Compact housing, 4 module=70 mm wide
  • Lockable cover
  • Measured values: P, U, I, KWh, PF, ... in 2 directions (solar panels)
  • 2x Pulse output and Modbus RTU output
  • Accuracy: MID B+D: Class I according to IEC 62053-21, Class B EN 50470-3
  • The default Modbus address (1–247) is entered via the display.
  • Default 9600 baud
This product includes:
  • 1 EMM.630 CT MID energy meter
  • Please note: The current transformers (type 1A or 5A) must be ordered separately.
Instruction manual:
Configuring the meter via the display:

To access the meter's setup menu, press and hold the bottom touch button until “password” appears. The default password is 1000. Use the up and down arrow keys (the second and third buttons) to change the first digit; press E briefly to move to the second digit; and press and hold the E button to confirm. Once logged in, you’ll see “set addr”; in the same way, you can now adjust the Modbus address and confirm by pressing and holding the E key a little longer. Next, press the down arrow to move to the next setup line and continue configuring the meter.

The same applies to the values of the coil to be connected. Here, you must set the secondary current to 1A or 5A, as well as the multiplication factor = primary-to-secondary current ratio

  • PLEASE NOTE: To prevent fraud, the coil type can only be entered once on the EMM.630 CT-MID; an incorrect entry will render the meter unusable:
Video

In the video below, we connect a CT-T16-100/1A current transformer. So here, Set Ct2=1A, and the multiplication factor from 1A to 100A is 100, so Ct rAtE= 0100.

ATTENTION: This setting can only be changed once!!

  • TIP: Try changing the mode address first to practice the procedure beforehand—after all, you can always change the mode address.
  • TIP: Here’s a summary of the key points for connecting and setting up this meter: Frequently Asked Questions - 2-Wire
Dimensions:
  • Packaging: 11 cm x 10 cm x 8 cm, 285 g
  • DIN-Rail: = 4 DIN rail modules
  • EAN: 5430000860109